Amending the Cross Connection Prevention and Control Ordinance

b

NOW, THEREFORE, BE IT ORDAINED BY THE BOARD, THE GOVERNING BODY OF THE WATER AUTHORITY:

Section 1.                     Section 8 is amended as follows:

                     Section 8.                      Cross Connection Prevention and Control

8-1-1 2.  SHORT TITLE.

                     This Ordinance shall be known and may be cited as “The Cross Connection Prevention and Control Ordinance.”

8-1-2 3.  APPLICABILITY.

                     Compliance with this Ordinance shall be a precondition to receiving or continuing to receive water service from the Water Authority public water system.

8-1-3 1.  PURPOSE AND POLICY.

(A)                     This Ordinance sets forth uniform requirements for, and applies to all customers of the Water Authority.

(B)                     The purpose of this ordinance is to enable the Water Authority to comply with applicable state and federal laws, including the Safe Drinking Water Act of 1974.

(C)                     The objectives of this Ordinance are to:

(1)                     Protect the public potable water supply from the possibility of contamination or pollution by isolating--within the customer’s internal distribution system or the customer’s private water system--such contaminants or pollutants which could backflow into the public water system; and

(2)                     Establish and maintain a Cross Connection control program that will systematically and effectively prevent the contamination or pollution of all potable water systems under the jurisdiction of the Water Authority.

(D)                     This Ordinance provides for monitoring, compliance and enforcement activities; establishes administrative and judicial review procedures; requires submission of test reports; and provides for the setting of fees for inspection and administration.

The purpose of this ordinance is to protect the public health, safety and welfare through the prevention and control of cross connections by:

                     (A)                     Protecting the public water system from contamination or pollution due to cross connections by containing the hazards at the service connection;

                     (B)                     Providing for the maintenance of a continuing program of cross-connection control that will systematically and effectively reduce the risk of the contamination of the public water system.

8-1-4.  DEFINITIONS.

                     For the purpose of this Ordinance, the following definitions shall apply unless the context clearly indicates or requires a different meaning.

                     APPROVED BACKFLOW PREVENTION ASSEMBLY.  An assembly or other means designed to prevent backflow. The assembly shall either be listed by the Foundation for Cross Connection Control and Hydraulic Research of the University of Southern California, or listed accepted by an ANSI Accredited Listing Agency.  All devices must be in compliance with the State of New Mexico Drinking Water Regulations.  The device the Water Authority and shall be limited to the following method and four (4) five types of assemblies unless otherwise stated:

                                          (1)                     AIR-GAP.  The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet conveying potable water into a tank, plumbing fixture, receptor and the flood level rim of the receptacle. An approved air gap shall be at least double the effective opening of the supply pipe or faucet and in no case, less than one (1) inch above the flood level.  An Air-Gap is the only Backflow Prevention method approved between potable water and sewage, and between reclaimed water and sewage.

                                          (2)                     PRESSURE VACUUM BREAKER.  Shall consist Consists of one independently operating spring-loaded check valve and an independently operating spring-loaded air inlet valve located on the discharge side of the check valve, two (2) full-ported, resilient seated shut-off valves and equipped with two (2) properly located resilient seated test cocks.

(3)                      REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY.  Shall consist Consists of two (2) independently acting check valves together with a hydraulically operating, mechanically independent pressure differential relief valve located between the check valves, including two (2) full-ported, resilient seated shut-off valves at each end of the assembly, and equipped with four (4) properly located resilient seated test cocks.  A reduced pressure principle backflow prevention assemble is approved for containment backflow prevention assembly.

(4)                     SPILL-RESISTAENT PRESSURE VACUUM BREAKER.  Shall consist Consists of one independently operating spring-loaded check valve and an independently operating spring-loaded air inlet valve located on the discharge side of the check valve, two (2)  full-ported, resilient seated shut-off valves and equipped with properly located resilient seated test cock and vent valve.

           (5)       DOUBLE CHECK VALVE ASSEMBLY.  Shall consist Consists of two (2) independently acting, approved check valves, including two (2) full-ported, resilient seated shut-off valves at each end of the assembly and equipped with four (4) properly located resilient seated test cocks.  Any existing double check valve assemblies are approved to continue in service provided that the assemblies can be maintained, tested and repair parts are available through the manufacturer.

ALTERNATE WATER SOURCE. Non-potable source of water that includes, but not limited to, gray water, on-site treated non-potable water, rainwater, and reclaimed (recycled) water.

AUXILIARY WATER SUPPLY. Any water source on or available to a premises other than the public water potable water from the Water Authority.  Auxiliary water supply may include water from another purveyor’s public potable water supply or any natural source such as a well.

                     BACKFLOW PREVENTION ASSEMBLY, CONTAINMENT.  An approved assembly installed in a customer’s water system to protect the public water system from an actual or potential threat of contamination or pollution of the public water system.  

                     BACKFLOW PREVENTION ASSEMBLY, ISOLATION.  An assembly installed within the customer's water system at the point of each cross connection to protect the customer’s potable water system from other non-potable water sources within the customer’s water system.                       

BACKFLOW.  The undesirable reversal of water flow.

BUILDING SUPPLY. The pipe carrying water from the public system or other source of water supply to a building or other point of use or distribution on the premises.

                     CERTIFIED BACKFLOW PREVENTION ASSEMBLY TESTER.  A person who is currently certified by the Water Authority to test backflow prevention assemblies.

                     CERTIFIED BACKFLOW PREVENTION ASSEMBLY REPAIRMAN.  A person who is a certified backflow prevention assembly tester and licensed by the appropriate mechanical classification to repair or replace backflow prevention devices in accordance with the New Mexico Construction Industries Licensing Act, NMSA 1978, §§60-13-1 through 60-13-59, NMSA 1978 and is holds a current certificate issued certified backflow prevention assembly tester by the Water Authority.

HAZARD, CONTAMINATION.  Contamination is any a hazardous substance that may cause death, illness, injury, or the spread of disease if introduced into a potable water system.  Contamination includes, but is not limited to, corrosion inhibitors; anti-freeze solutions; chemical water treatment for boilers and cooling systems; fertilizers, herbicides and pesticides used in irrigation systems; heavy metals and total coliform bacteria found in fire systems; and other hazardous substances.

                     CROSS CONNECTION.  An actual or potential connection between a potable water system and a non-potable water source.

                     CROSS CONNECTION CONTROL CONTAINMENT.  The protection of the public water system by the installation of an approved backflow prevention assembly at each service connection to a customer's water system from the public water system.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection, unless protected by a Backflow Prevention Assembly. and accepted by the Water Authority.

                     CROSS CONNECTION CONTROL ISOLATION.  The protection of the customer’s water system by the installation of an approved backflow prevention assembly within the customer's water system at the point of each and every cross-connection.

                     CROSS CONNECTION ADMINISTRATOR.  The person designated by the Water Authority to administer the cross connection control program and who is charged with certain duties and responsibilities by this Ordinance.

                     CROSS CONNECTION ENGINEER.  The person designated by the Executive Director of the Water Authority as a technical expert in cross connection matters responsible for enforcing the Cross Connection Control Ordinance. and to help the Cross Connection Program Manager enforce the cross connection control ordinance. The Cross Connection Engineer shall be a registered professional engineer in accordance with the State of New Mexico Board of Licensure for Professional Engineers and Surveyors, pursuant to the Engineering and Surveying Practice Act, NMSA 1978,  §§ 61-23-1 through 61-23-32, NMSA 1978 and meet all the requirements of the job description approved by the Executive Director and be a certified backflow prevention assembly tester.

                     CROSS CONNECTION OPERATIONS AND MAINTENANCE SUPERVISOR/ INSPECTOR.  The person(s) designated by the Water Authority to assist the Cross Connection Program Manager in the enforcement of the cross connection control Ordinance and who is charged with certain duties and responsibilities by this Ordinance.  The Cross Connection Operations and Maintenance Supervisor/Inspector shall be a certified Water Operator Level IV and be a certified backflow prevention assembly tester.

                     CROSS CONNECTION PROGRAM MANAGER. The person designated by the Water Authority to enforce the cross connection control Ordinance and who is charged with certain duties and responsibilities by this Ordinance. The Cross Connection Program Manager shall be a certified Water Operator Level IV and be a certified backflow prevention assembly tester.

CUSTOMER. Any person, association, corporation, or entity receiving Water Utility service, related products or services in the Service Area. Any The person responsible for payment of fees as determined pursuant to the Albuquerque Bernalillo County Water Utility Authority Water and Sewer Rates Ordinance as it may be amended.

                     CUSTOMER'S WATER SYSTEM.  The water system on a customer's premises beginning at the service connection.

DOMESTIC SERVICE.  Service line for potable drinking water.

                     EXECUTIVE DIRECTOR.  The Executive Director of the Water Authority or his/her designee.

                     NON-RESIDENTIAL WATER CUSTOMER.  Any water customer who is served by the public water system and is classified in the Albuquerque Bernalillo County Water Utility Authority Water and Sewer Rates Ordinance as follows:

                                          (1)                     Commercial. Retail, offices, hotels, motels, shopping centers, none of which use process water in the conduct of business.

                                          (2)                     Industrial. Manufacturing or process facility, which is engaged in producing a product.

                                          (3)                     Institutional. Government buildings, hospitals, schools, and other facilities that provide public and quasi-public services.                     

                                          (4)                     Multifamily dwelling of three (3) or more stories.

HAZARD, POLLUTION.  A low hazard substance that will degrade the taste, color, odor or other aesthetic quality of the water if introduced into a potable water system, but will not cause death, injury or spread of disease. Pollution includes, but is not limited to, backflow of domestic water from tall buildings; backflow of domestic hot water from water heaters; and other similar low hazard substances.

PREMISES.  A building, a tract of land with buildings, or parts of buildings thereon.

PRIVATE FIRE PROTECTION SYSTEM. A Private Fire Protection System begins at the property boundary or at the water utility easement boundary to a customer’s premises.  The Private Fire Protection System includes sprinkler, hose connections, hydrants, reservoirs, tanks, standpipes, pumps, distribution pipes, and other appurtenances within premises that are owned, operated and maintained by the customer for the purpose of fire suppression.

                     PUBLIC WATER SYSTEM.  The potable water system that supplies water service to residential and non-residential water customers users within the service area of the Water Authority.

                     RESIDENTIAL WATER CUSTOMER.  Any water customer who is served by the public water system and classified in the Albuquerque Bernalillo County Water Utility Authority Water and Sewer Rates Ordinance as follows:

(1)                     single-family detached,

(2)                     townhouses served by individual meters,

(3)                     duplexes served by individual meters

(4)                     condominiums served by individual meters

(5)                     triplexes served by common or individual meters,

(5)                     mobile homes served by individual meters or for the purpose of the Cross Connection Ordinance

(6)                     multi-family dwelling of less than three (3) stories

                     

SERVICE AREA.  Those parts of Bernalillo County and contiguous territory served by the Water Authority.

SERVICE CONNECTION.  The terminal end of the water service from the public water system and point of delivery to the customer’s water system, more particularly defined as follows:

                                          (1)                     The service connection for a metered water service is the downstream end of the water meter or meter setter;

                                          (2)                     The service connection for un-metered water services and fire lines which serve private fire protection systems is located at the property boundary or at the water utility easement boundary to a customer's premises; or and

                                          (3) The service connection for a fire hydrant and all other temporary or emergency water services that is located at the point of connection to the public water system.

SEWAGE.  Wastewater and excrement conveyed in sewers.

WATER AUTHORITY.  The Albuquerque Bernalillo County Water Utility Authority.

                     WATER, NONPOTABLE. Water that does not meet federal and state drinking water standards.  Water that is not safe for human consumption or that is of questionable quality.  Any water delivered by the non-potable water system and intended for irrigation, industrial or used for or other allowable non-potable applications.

WATER, POTABLE. Water delivered by the public water system intended for human consumption and meeting federal and state drinking water standards.

                     WATER, USED.  Any water delivered by the public water system to a customer's water system after it has passed the service connection.

8-1-5.  ADOPTION OF TECHNICAL SPECIFICATIONS.

                     The Water Authority shall may adopt technical specifications to define backflow prevention assembly installation standards from, but not limited to, the International Association of Plumbing and Mechanical Officials (IAPMO) Uniform Plumbing Code (UPC), and the University of Southern California Manual of Cross Connection Control. guidelines and criteria.  The Water Authority shall update the current Manual of Procedures and the Water Authority’s portion of the City of Albuquerque’s Standards and Specifications for Public Works Construction to incorporate the provisions of this Ordinance.

8-1-6.  RESPONSIBILITY.

                     It shall be the responsibility of the Water Authority to administer and enforce the provisions of this Ordinance.  This Ordinance also assigns responsibilities to customers, and to certified backflow prevention assembly testers and repairmen as described in this section.

                     (A)                     Water Authority.  The Water Authority shall be responsible for the protection of the public water system from contamination or pollution due to the backflow of contaminants or pollutants through the water service connection.  The Water Authority shall enforce all the provisions of this Ordinance that relate to cross connection control by containment; shall approve all cross connection control backflow prevention assemblies; shall administer a continuing cross connection containment control program; maintain a customer and current backflow prevention assembly data base; and shall not knowingly install, maintain or approve installation of a water service connection unless the public water system is protected as required by this Ordinance.  

                     (B)                     Customer. All customers shall be responsible, without further notice, for the prevention of contaminants, pollutants, water from alternate sources, or water from auxiliary water supplies from entering the customer's potable water system and the public water system.  Customers shall provide approved backflow prevention assemblies as required by local plumbing codes and this Ordinance.  Regardless of the location of the containment backflow prevention assembly, the customer’s responsibility begins at the service connection and extends throughout the entire length of the water system within the premises.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection.  Customers shall install, have tested, and maintain, at their own expense, backflow prevention assemblies as directed by the Water Authority.  Test reports shall be delivered to the Water Authority within seven (7) calendar days of testing. Accurate records of all inspections, tests, repairs and replacement of backflow prevention assemblies shall be maintained by the customer for a period of three (3) years.

                     (C)                     Certified backflow prevention assembly tester. Only certified backflow prevention assembly testers are permitted to inspect and test backflow prevention assemblies. They shall complete and provide accurate test reports to the Cross Connection Manager and Customer.  They shall Water Authority within seven (7) calendar days of the test, submit test gauge reports to the customer and submit calibration test reports annually to the Cross Connection Manager Water Authority. They shall report to the customer and the Cross Connection Manager Water Authority any discovered discrepancies or violations that which the tester may have observed during the course of testing a backflow prevention assembly.

                     (D)                     Certified backflow prevention assembly repairman. Only certified backflow prevention assembly repairmen are permitted to inspect, repair, replace, and test backflow prevention assemblies. They shall complete and provide accurate test reports to the Cross Connection Manager and customer.  They shall Water Authority within seven (7) calendar days of the test, submit test gauge calibration certification reports annually to the Cross Connection Manager.  They shall report to the customer and the Cross Connection Manager submit calibration test reports annually to the Water Authority. Report to the customer and the Water Authority any discovered discrepancies or violations which the repairman may have observed during the course of testing and or repairing a backflow prevention assembly.  Such repairman shall not change the design, material or operational characteristics of a backflow prevention assembly without prior approval of the Cross Connection Manager Water Authority.

8-1-7.  REQUIREMENTS.

                     (A)                     Mandatory cross connection control by containment:

                                          (1)                     Effective February 15, 2009 all new non-residential premises must shall have a containment reduced pressure principle backflow prevention assembly approved by the Water Authority installed after the at each domestic service connection to the customer’s water system or at a location approved by the Water Authority, as set forth in the UPC and this Ordinance.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection unless protected by a Backflow Prevention Assembly Uniform Plumbing Code.

                      (2)       Effective February 15, 2009 all remodeled  non-residential premises, when the work area of the building undergoing repairs, alterations or rehabilitation, as defined in the International Existing Building Code, exceeds 50 percent of the aggregate area of the building regardless of the costs of repairs, alteration, or rehabilitation, shall must have a containment reduced pressure principle backflow prevention assembly approved by the Water Authority installed after the at each domestic service connection to the customer’s water system or at a location approved by the Water Authority, as set forth in the UPC and this Ordinance.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection unless protected by a Backflow Prevention Assembly Uniform Plumbing Code.

                                          (3)                     All construction premises with temporary service connection shall have a containment reduced pressure principle backflow prevention assembly approved by the Water Authority installed at each temporary service connection to the construction site, as set forth in the UPC and this Ordinance.

(43)                     All non-residential irrigation water systems connected to the public water system shall must have a pressure vacuum breaker, spill-resistant pressure vacuum breaker or a reduced pressure principle backflow prevention assembly installed after at the service connection on the public water system.  Such devices shall be approved by the Water Authority.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection.

 at the potable service connection.

                                          (45)                     All non-residential customers connected via piping to an alternative a non-potable water source or an auxiliary water supply system and the public water system shall install a containment reduced pressure principle backflow prevention assembly approved by the Water Authority after the potable service connection.

(56                     All fire hydrants used for drawing water for filling tanks and tank trucks and for temporary irrigation systems must have an air-gap or approved containment reduced pressure principle backflow prevention assembly in accordance to the Manual of Procedures and approved by the Water Authority, as set forth in the UPC and this Ordinance.

                                          (67)                     Any residential premises having existing private wells and who desire to connect to the public water system shall have two (2) options as follows:

                                                               (a)                     Customers shall permanently abandon the use of private wells by plugging the wells as accepted by the Water Authority prior to connecting to the public water system; or

                                                               (b)                     Customers who choose to maintain their private wells shall completely sever the private well from the premises’ potable plumbing system.  and shall install a reduced pressure principle backflow prevention assembly approved by the Water Authority at the terminal end of the water service from the public water system (e.g., service connection)

(78)                     Effective February 15, 2009,  all new  fire line services to private fire protection systems shall be equipped with a containment reduced pressure principal backflow prevention assembly approved by the Water Authority and Fire Marshal having jurisdiction installed after the at each service connection.  No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection. A double check valve assembly approved by the Water Authority and Fire Marshal having jurisdiction may be installed instead of a reduced pressure backflow prevention assembly provided the private fire protection system meets or exceed contains ANSI/NSF Standard 60 and or 61 water piping throughout the entire private fire protection system, the fire sprinkler drain discharges into atmosphere, and there are no reservoirs, fire department connections nor-connections from auxiliary water supplies, antifreeze nor other additives.

                                          (89)                     Premises with existing private fire protection systems containing double check valve assemblies installed and approved by the Water Authority prior to 2009 are approved to continue in service as long as the device tests and functions properly.

                                          (910)      Effective February 15, 2009 all remodeled  non-residential premises, when the work area of the building undergoing repairs, alterations or rehabilitation, as defined in the International Existing Building Code, exceeds 50 percent of the aggregate area of the building regardless of the costs of repairs, alteration, or rehabilitation with existing private fire protection systems without a containment any backflow prevention assemblies shall must be retrofitted with an approved reduced pressure principle backflow prevention double check valve assembly approved by the Water Authority and Fire Marshal having jurisdiction.  Assembly shall be installed at each private fire protection after the service connection to the customers water system. Approved reduced pressure principle backflow prevention assembly shall  double check valve assemblies must be installed by a person who is licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act. Fire sprinkler system hydraulic performance shall must be verified by an engineer registered in accordance with the State of New Mexico Board of Licensure for Professional Engineers and Surveyors, pursuant to the Engineering and Surveying Practice Act, NMSA 1978 §§ 61-23-1 through 61-23-32, NMSA 1978

                                          (1011)                     Once an approved backflow prevention assembly is for containment has been installed at a premises, as a cross connection control containment assembly, the assembly shall not be removed without prior approval from the Water Authority,  customer, Containment the backflow prevention tester or the backflow prevention repairman shall not have the device removed. Permanent removal of a containment backflow prevention assembly will result in termination of water service and/or revocation of backflow certification. Backflow prevention assemblies that cannot be repaired must be replaced in-kind per the terms of this Ordinance.

                                          (1112) Once an approved backflow prevention assembly assemblies may be for containment has been properly installed the assembly shall not be modified inside or outside the premise.                                          

                     (B)                     Inspection of premises.

                                          (1)                     Right of entry.  Whenever necessary to make an inspection to enforce any of the provisions of this Ordinance, or whenever the Water Authority or its authorized representative has reasonable cause to believe that there exists in any building or upon any premises, any condition which may endanger the public water supply makes such building or premises unsafe as defined in this Ordinance, the Water Authority or its authorized representative may enter such building or premises at reasonable times to inspect the same or to perform any duty imposed upon the Water Authority by this Ordinance; provided that if such building or premises be occupied, the Water Authority representative will he/she shall first present proper credentials and demand entry; and if such building or premises be unoccupied, the Water Authority representative will shall first make a reasonable effort to locate the owner or other persons having charge or control of the building or premises and demand entry.  If entry and or inspection is refused, the Water Authority may shall immediately terminate water service to the premises.

                                          (2)                     Inspection of premises.  The Water Authority shall schedule an inspection at a reasonable date and time and give the customer written notice prior to an inspection.  The purpose and authority to conduct such an inspection shall be disclosed to in the customer notice.  If actual or potential cross connections, which could result in backflow of contaminants, pollutants, and water from auxiliary water supplies or water from the non potable water systems through the water service connection and into the public water system, are determined to exist during the premises inspection, the Water Authority shall evaluate the hazards and proceed as follows:

                                                               (a)                     In the event a contamination of the public water supply hazard is determined to exist, the Water Authority shall immediately terminate water service to the premises.  The Water Authority shall restore water service to the premises once the contamination hazard has been controlled or eliminated.

                                                               (b)                     In the event no contamination is hazard or substantial dangers are determined to exist, but actual or potential cross connections require control by containment, the Water Authority shall give the customer written notice to install an approved reduced pressure principle backflow prevention assembly as a cross connection control containment assembly after at the service connection at the customer’s own expense.  The backflow assembly shall be installed, inspected and tested within fifteen (15) calendar days from the date of the notice.  For good cause, the Water Authority may extend the time to comply with the requirements of this Ordinance.

                     (C)                     Re-inspection.  Re-inspection of premises shall be conducted by the Water Authority to verify corrective action has been implemented as required by this Ordinance.

                     (D)                     Installation of backflow prevention assemblies.  Any contractor licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act may install backflow prevention assemblies in accordance with the UPC and this Ordinance Manual of Procedures.  The contractor shall be responsible for obtaining all required approvals, such as approved plans, permits and inspections. Such contractor shall not change the design, material or operational characteristics of a backflow prevention assembly without prior approval of the Water Authority.

                     (E)                     Tests and maintenance of backflow prevention assemblies.  Customers shall have their existing containment and isolation backflow prevention assemblies tested at least once a year by a certified backflow prevention assembly tester.  Assemblies that fail a test shall be repaired or replaced by a certified backflow prevention assembly repairman and immediately retested by a certified backflow prevention assembly tester repairmanA test report shall be submitted to the customer and the Water Authority within seven (7) calendar days of test, or the test will be void, and retesting will be required. Tests and repairs shall be at the expense of the customer.

                     All new installations of backflow prevention assemblies shall be tested immediately upon installation (if/when water service is available) and test reports submitted to the Water Authority within seven (7) calendar days or the tests will become void and retesting would be required.  Once the backflow prevention assembly is tested and operating properly, water service to the premises may continue.  Water Authority shall inspect all newly installed containment backflow prevention assemblies.

                     The repairman and tester shall use separate tools and gauges for testing backflow prevention assemblies on potable water systems, such tools and gauges are never to be used on non-potable water, including alternate water sources. They shall submit all test reports to the Water Authority and customer with seven (7) calendar days of the test, or the test becomes void, and retesting of assembly would be required.  The customer shall submit all test reports to the Water Authority.  The Water Authority shall provide the test report form to customers, certified backflow prevention assembly testers, and repairmen upon request.  They shall submit test gauge calibration test report annually to the Cross Connection Manager.  Tests performed with a test gauge that has not had a yearly calibration certification are void.  Accurate records of all inspections, tests, repairs, and replacement of backflow prevention assemblies shall be maintained by the customer for a period of three (3) yearsand repairmen.

                     (F)                     Existing previously approved backflow prevention assemblies.  Any existing backflow prevention assemblies that were previously are not on the current list of approved backflow prevention assemblies may be approved to continue in service provided that the assemblies test and function properly. When required, can be maintained, tested and repaired with parts available through the manufacturer.  Whenever obsolete assemblies are replaced, they shall be replaced with current, approved backflow prevention assemblies.

                     (G)                     Certification of testers and repairmen.  To be certified as a backflow prevention assembly tester, a person shall attend a training course that has been approved by the Water Authority and successfully complete the written and practical examinations administered as part of the approved training course.  A person who is licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act and attends and successfully completes the approved training course may be certified as a backflow prevention assembly repairman.

                     (H)                     Re-certification of testers and repairmen.  A certified tester or repairman who wishes wants to remain active as a backflow assembly tester or repairman shall renew their certification every three (3) years.  To re-certify, prior to existing certification expiring, testers and repairmen must complete have the following options:  (1) Complete an approved 40-hour training course; or (2) Complete an approved eight (8) hour training course and accrue sixteen (16) hours of approved continuing education credits. Otherwise, the certified tester or repairman must complete an approved 40-hour training course.  Testers or repairmen with non-expired certifications shall provide proof of training credits earned and training course attended prior to re-certification.

                     (I)                     Approved training courses.  The Water Authority shall approve training courses.  The approved course shall be conducted by an instructor who is a certified tester and or repairman; duration of the course shall be at least forty (40) hours; and the minimum material covered shall either be based on the University of Southern California's Foundation for Cross Connection Control and Hydraulic Research training course or an ANSI accredited listing agency.

                     The approved re-certification training course shall be conducted by an instructor who is a certified tester and or repairman; duration of the course shall be at least eight (8) hours and the course shall include rules, regulations, the Cross Connection Ordinance, and minimum of six (6) hours practical training and practical examinations.

                     The instructor conducting the certification and re-certification courses shall administer the written and practical examinations.  A performance of over 70% on the written examination and satisfactory completion of the practical examination constitutes successful completion of the course.

Administrator of the approved training course or approved recertification training course shall submit the course syllabus once a year, or upon any changes to the syllabus for approval by the Water Authority.

                     (J)                     Revocation.  The Water Authority shall revoke certification of any certified backflow prevention assembly tester or repairman for any of the following reasons: 

(1)   falsification of tests, records or reports;

(2)   failure to properly maintain test equipment;

(3)   failure to submit calibration test report annually; 

(4)  alterations of an existing backflow prevention assembly without the approval of the Water Authority; or

(5)  failure to inform the Water Authority of an existing cross connection or a fire protection system without an approved backflow prevention assembly.

8-1-8.  FEES.

                     The Water Authority shall assess fees associated with the implementation of this Ordinance as determined and set by the Water Authority Water and Sewer Rate Ordinance. The fees imposed by this Ordinance are as follows:

                     (A)                     Inspection fees.  An inspection fee plus applicable gross receipts tax may shall be assessed for an inspection conducted on the customer’s premises.  The fee shall be assessed only to those customers whose premises are not in compliance with this Ordinance at the time of inspection and to recover the expenses incurred by the Water Authority to inspect the premises.

                     (B)                     Administrative fees.  All customers shall be assessed an annual administrative fee plus applicable gross receipts tax for each backflow prevention assembly located at the premises.  The fee shall recover the expenses incurred by the Water Authority to maintain records, process notices, enter test results and maintain the database.

(C)                     Late report fees.  If a passing test report is not submitted by the due date, a late report fee may be assessed, beginning 30 days after the due date.  (Per the Requirement Section above, the test report is only valid for seven (7) days after testing.

(D)                     Non-existent containment backflow preventer assembly fee.  Non-exempt service connections, which do not have a containment backflow preventer assembly, or have an unapproved backflow preventer assembly, may be assessed a containment backflow preventer assembly fee when the second notice of violation is issued for lack of an approved containment backflow preventer assembly.

(E)                     Unauthorized connection fee.  Unauthorized tees, branches, connection fittings, or openings between the containment backflow prevention assembly and the service connection, may be assessed an unauthorized connection fee when the second notice of violation is issued for an unauthorized connection.

 

(F)                     Ordinance documents.  Copies of this Ordinance may be obtained at the Water Authority website.  City Treasurer, Albuquerque/Bernalillo County Government Center for a fee.

                     Manual of Procedures.  Copies of the Manual of Procedures may be obtained at the City Treasurer, Albuquerque/Bernalillo County Government Center, and Albuquerque, New Mexico for a fee.

                     (GE)                     Payment.  All fees shall be payable to the office of the Water Authority Customer Services Division, Albuquerque/Bernalillo County Government Center, Albuquerque, New Mexico, and will become delinquent fifteen (15) days following the due date on the customer's statement. 

                     (HF)                     Penalty.  A penalty of 1.5% per month shall be imposed on all delinquent accounts.

                     (IG) Responsibility of payment, liens and deposit.  The persons responsible for payment of the fees included in this Ordinance shall be the customer upon whom charges are imposed under with the Water Utility Authority Water and Sewer Rates Ordinance as it may be amended.

8-1-9.  PENALTIES AND VIOLATIONS ALTERNATE METHODS TO ACHIEVE COMPLIANCE.

                     (A)                     Notice of Violation.  When the Cross Connection Manager finds that a customer has violated, or continues to violate, any provision of this Ordinance or order issued by the Cross Connection Manager or Engineer, the Cross Connection Engineer may serve upon the customer a written notice of violation.  Within fifteen (15) days after receipt of the notice of violation, the customer shall give the Cross Connection Engineer an explanation of the violation and a plan for correcting and preventing the violation, including the specific actions that may be required.  Submission of a plan shall not relieve the customer of liability for any violations occurring before or after receipt of the notice of violation. 

(B)                     Customers issued a third notice of violation may be required to relocate the containment backflow prevention assembly next to the water meter, property line or easement line.

(C)                     Revocation.  The Water Authority may suspend or revoke a tester’s certification for any of the following:

                     (1)                     falsification of tests, records or reports;

                     (2)                     failure to properly maintain test equipment;

                     (3)                     failure to submit test gauge calibration test report annually;

                     (4)                      recurrent submittal of inaccurate or incomplete test reports;

                     (5)                     alterations or removal of an existing backflow prevention assembly without the approval of the Water Authority;

                     (6)                     failure to inform the Water Authority of an observed cross connection; or

                                          (7)                     certified backflow prevention assembly tester/repairman is working outside of his/her certification.

(A)                     Remote installations of containment backflow prevention assemblies.  In instances where the containment backflow prevention assembly(ies) cannot be installed at the service connection, the customer may install the approved backflow prevention assembly(ies) at a remote location with the approval of the Cross Connection Engineer or the Cross Connection Program Manager.

8-1-10.  GROUNDS FOR TERMINATION OF WATER SERVICE UNDER THIS ORDINANCE.

                     (A)                     Any person who willfully removes, modifies or bypasses any approved backflow prevention assembly without prior approval of the Water Authority, falsifies tests records or reports, obtains water from a fire hydrant in violation of cross connection control requirements, connects an alternate water source to potable water a building fire protection service, connects an auxiliary water supply to potable to a normal water service, or connects Water Authority reclaimed water to non-potable water without approved backflow protection, thus creating a cross connection, or otherwise violates any provision of this Ordinance may have water service terminated.

                     (B)                     In the event the Cross Connection Engineer or Cross Connection Program Manager determines that a potential contamination exists and may be a threat to the public water system, water service to the premises shall be terminated immediately.  The Water Authority shall restore water service to the premises once the customer has controlled or eliminated the contamination hazard.

                     (C)                     Failure to install required backflow prevention assemblies as directed by the Water Authority, failure to conduct required tests, failure to submit accurate test reports within seven (7) calendar days of the test, failure to perform testing and maintenance of backflow prevention assemblies, or failure to allow the Water Authority entry into a premises shall constitute grounds for termination of water service to the premises.  Service shall not be restored until such conditions or defects are corrected.  If water service is terminated for any of these reasons, a turn-off and turn-on water service fee will be assessed to the customer as per the Albuquerque Bernalillo County Water Utility Authority Water and Sewer Rates Ordinance.

                     (D)                     The Water Authority may terminate water service for non-payment of the fees included in this Ordinance and in accordance with the Albuquerque Bernalillo County Water Utility Authority Water and Sewer Rates Ordinance as it may be amended.

8-1-11.  TERMINATION OF WATER SERVICE; HEARING.

                     (A)                     The Cross Connection Engineer or the Cross Connection Program Manager may terminate the water service to the property for failure on the part of the customer to comply with any provision of this Ordinance.

(B)                     In order to terminate service, a written notice shall be sent to the customer giving him/her at least ten (10) calendar days’ notice of the proposed termination of water service and notice of his/her right to protest the Cross Connection Engineer’s or Cross Connection Program Manager’s action at a hearing. 

(C)                      In the event a hearing is requested, the water service shall not be terminated until and in accordance with the decision of the hearing officer. However the Cross Connection Engineer or Cross Connection Program Manager shall immediately terminate water service to the premises in the event that contamination is determined to exist or entry for an inspection to a premises is denied.

(D)                     The customer must request that a hearing be held by delivering such request in writing to the Executive Director on or before the date the water services are to be terminated.  In the case of immediate termination,  such written request shall be delivered within ten (10) calendar days after the date of termination.

                     (E)                     At such hearing, the customer may present evidence as the Hearing Officer finds relevant. The Hearing Officer shall make findings, conclusions and recommendations to the Executive Director. The Executive Director may affirm, overrule or modify the decision to terminate the services.  The decision shall be final.

                     (F)                     A non-refundable hearing fee of $50.00 shall accompany each request for hearing pursuant to this Section.

                     Section 2.                     SEVERABILITY CLAUSE.  If any section, paragraph, sentence, clause, work or phrase of this Ordinance is for any reason held to be invalid or unenforceable by any court of competent jurisdiction, such decision shall not affect the validity of the remaining provisions of this Ordinance.  The Authority hereby declares that it would have passed this Ordinance and each Section, paragraph, sentence, clause, word or phrase thereof irrespective of any provision being declared unconstitutional or otherwise invalid.

Section 3.                     EFFECTIVE DATE AND PUBLICATION.   This Ordinance shall become effective August 1, 2018, after publication by title and general summary.